Kyoritsu Leakage Clamp Meters KEW 2413F
Extra wide transformer jaws are best suited for clamping on all three or four wires (3 phases) together for leakage current measurement. Features a frequency filter switch to eliminate the effect of harmonics.
The standout feature of the KEW 2413F is its ability to accurately measure leakage current, making it an invaluable tool for detecting and diagnosing electrical faults and insulation problems in both residential and industrial settings.
Kyoritsu KEW 2413F specifications:
- AC A (50/60Hz): 200mA/2/20/200A/1000A
±1.5%rdg±2dgt (200mA/2/20A)
±2%rdg±2dgt (200A 0 – 500A)
±5.5%rdg (501 – 1000A)
- AC A (WIDE): 200mA/2/20/200/1000A
±1%rdg±2dgt [50/60Hz],
±3%rdg±2dgt [40Hz – 1kHz] (200mA/2/20A)
±1.5%rdg±2dgt [50/60Hz],
±3.5%rdg±2dgt [40Hz – 1kHz] (200A/0 – 500A)
±5%rdg [50/60Hz],
±10%rdg [40Hz – 1kHz] (501 – 1000A)
- Conductor size: Ø68mm max.
- Frequency response: 40Hz – 1kHz
- Output: Waveform :
AC200mV against the maximum value of each range (1000A range is 100mV)
Recorder :
DC200mV against the maximum value of each range (1000A range is 100mV)
- Applicable standards: IEC 61010-1 CAT III 300V
IEC 61010-2-032
Related Product